Display, buttons and LEDs

Data sheet

Name
agc-150-ats-data-sheet-4921240628-uk
Product
AGC 150 ATS
No. Name Function
1 Power

Green: The controller power is ON.

OFF: The controller power is OFF.

2 Display screen

Resolution: 240 x 128 px.

Viewing area: 88.50 x 51.40 mm.

Six lines, each with 25 characters.

3 Navigation Move the selector up, down, left and right on the screen.
4 OK

Go to the Menu system.

Confirm the selection on the screen.

5 Back Go to the previous page.
6 AUTO mode

The controller automatically connects and disconnects the breakers. In genset applications, the controller also automatically starts and stops, the genset. No operator actions are needed.

7 Silence horn Stops an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the ATS priority selection, Jump menu, Mode selection, Lamp test.
9 SEMI-AUTO mode

The operator or an external signal can connect or disconnect the breaker, and in genset applications, start and stop the genset. The controller cannot automatically connect or disconnect the breaker, or start and stop the genset.

The controller automatically synchronises before closing a breaker.

10 Close breaker Push to close the breaker. In genset applications, the genset is automatically started when you push this button before closing the breaker.
11 Open breaker Push to open the breaker. In genset applications, the genset is automatically stopped when you push this button before opening the breaker.
12 Breaker symbols

Green: Breaker is closed.

Green flashing: Synchronising.

Red: Breaker failure.

14 Load symbol

Green: The supply voltage and frequency are OK.

Red: Supply voltage/frequency failure.