Protections overview

Data sheet

Name
agc-150-ats-data-sheet-4921240628-uk
Product
AGC 150 ATS
Protections Alarms ANSI Operate time
Reverse power 2 32R <200 ms
Fast over-current 2 50P <40 ms
Over-current 4 50TD <200 ms
Voltage dependent over-current 1 50V  
Over-voltage 2 59 <200 ms
Under-voltage 3 27P <200 ms
Over-frequency 3 81O <300 ms
Under-frequency 3 81U <300 ms
Unbalanced voltage 1 47 <200 ms
Unbalanced current 1 46 <200 ms
Loss of excitation or reactive power import 1 32RV <200 ms
Over-excitation or reactive power export 1 32FV <200 ms
Overload 5 32F <200 ms
Inverse time earth over-current 1 50G <100 ms
Inverse time neutral over-current 1 50N <100 ms
Emergency stop 1   <200 ms
Low auxiliary supply 1 27DC  
High auxiliary supply 1 59DC  
Breaker 1 (CB1) external trip 1    
Breaker 2 (CB2) external trip 1    
BTB breaker external trip 1    
Synchronisation failure alarms      
Breaker open failure 1/breaker 52BF  
Breaker close failure 1/breaker 52BF  
Breaker position failure 1/breaker 52BF  
Close before excitation failure 1    
Phase sequence error 1 47  
Hz/V failure 1    
Not in Auto 1    
Positive sequence (mains) voltage low 1 27 <60 ms
Directional over-current 2 67 <100 ms
Negative sequence voltage high 1 47 <400 ms
Negative sequence current high 1 46I2 <400 ms
Zero sequence voltage high 1 59U0 <400 ms
Zero sequence current high 1 50I0 <400 ms
Power-dependent reactive power 1 40 -
IEC/IEEE inverse time over-current 1 51 -