Electrical specifications

Data sheet

Name
agc-150-ats-data-sheet-4921240628-uk
Product
AGC 150 ATS
Power supply
Power supply range

Nominal voltage: 12 V DC or 24 V DC

Operating range: 6.5 to 36 V DC

Voltage withstand Reverse polarity
Power supply drop-out immunity 0 V DC for 50 ms (coming from min. 6 V DC)
Power supply load dump protection Load dump protected according to ISO16750-2 test A
Power consumption

5 W typical

12 W max.

RTC clock Time and date backup
Supply voltage monitoring
Measuring range

0 V to 36 V DC

Max. continuous operating voltage: 36 V DC

Resolution 0.1 V
Accuracy ±0.35 V
Voltage measurement
Voltage range Nominal range: 100 to 690 V phase-to-phase (above 2000 m derate to max. 480 V)
Voltage withstand

Un +35 % continuously, Un +45 % for 10 seconds

Measuring range of nominal: 10 to 135 %

Low range, nominal 100 to 260 V: 10 to 351 V AC phase-to-phase

High range, nominal 261 to 690 V: 26 to 932 V AC phase-to-phase

Voltage accuracy

±1 % of nominal within 10 to 75 Hz

+1/-4 % of nominal within 3.5 to 10 Hz

Frequency range 3.5 to 75 Hz
Frequency accuracy

±0.01 Hz within 60 to 135 % of nominal voltage

±0.05 Hz within 10 to 60 % of nominal voltage

Input impedance 4 MΩ/phase-to-ground, and 600 kΩ phase/neutral
Current measurement
Current range

Nominal: -/1 A and -/5 A

Range: 2 to 300 %

Number of CT input 4
Max. measured current

3 A (-/1 A)

15 A (-/5 A)

Current withstand

7 A continuous

20 A for 10 seconds

40 A for 1 second

Current accuracy
From 10 to 75 Hz:
  • ±1 % of nominal from 2 to 100% current
  • ±1 % of measured current from 100 to 300 % current
From 3.5 to 10 Hz:
  • +1/-4 % of nominal from 2 to 100 % current
  • +1/-4 % of measured current from 100 to 300 % current
Burden Max. 0.5 VA
Power measurement
Accuracy power ±1 % of nominal within 35 to 75 Hz
Accuracy power factor ±1 % of nominal within 35 to 75 Hz
Digital inputs
Number of inputs

12 x digital inputs

Negative switching

Maximum input voltage +36 V DC with respect to plant supply negative
Minimum input voltage -24 V DC with respect to plant supply negative
Current source (contact cleaning) Initial 10 mA, continuous 2 mA
DC outputs
Number of 3 A outputs

2 x outputs

15 A DC inrush and 3 A continuous, supply voltage 0 to 36 V DC

Endurance tested according to UL/ULC6200:2019 1.ed: 24 V, 3 A, 100000 cycles (with an external freewheeling diode)

Number of 0.5 A outputs

10 x outputs

2 A DC inrush and 0.5 A continuous, supply voltage 4.5 to 36 V DC

Common 12/24 V DC
Analogue inputs
Number of inputs 4 x analogue inputs
Electrical range Configurable as:
  • Negative switching digital input
  • 0 V to 10 V sensor
  • 4 mA to 20 mA sensor
  • 0 Ω to 2.5 kΩ sensor
Accuracy
Current:
  • Accuracy: ±20 uA ±1.00 % rdg
Voltage:
  • Range: 0 to 10 V DC
  • Accuracy: ±20 mV ±1.00 % rdg
RMI 2-wire LOW:
  • Range: 0 to 800 Ω
  • Accuracy: ±2 Ω ±1.00 % rdg
RMI 2-wire HIGH:
  • Range: 0 to 2500 Ω
  • Accuracy: ±5 Ω ±1.00 % rdg
Display unit
Type Graphical display screen (monochrome)
Resolution 240 x 128 pixels
Navigation Five-key menu navigation
Log book Data log and trending function
Language Multi-language display