Protections in general

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS

All protection set points are a percentage of the nominal values.

For most of the protections a set point and time delay is selected. When the timer runs out, the output is activated. The operate time is the delay setting + the reaction time.

When setting up the controller, the measuring class of the controller and an adequate safety margin has to be taken into consideration, for example:
  • A power generation system must not reconnect to a network when the voltage is < 85 % of UNOM ±0 % or > 110 % ±0 %. To ensure reconnection within this interval, the controller’s tolerance/accuracy has to be taken into consideration. If the reconnection tolerance is ±0 %, set a controller’s set points 1-2 % higher/lower than the actual set point.

General parameter ranges for protections

Setting Range
Output A

Not used

12 relays: 5, 6, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18

External I/O: Relays available in the connected CIO(s)

Limits

Output B
Enable

OFF

ON

Fail class See the controller type

Inhibits

You can only select inhibits using the utility software. Each alarm has a selection list for the inhibit conditions. Inhibit of the alarm is active as long as one of the selected inhibit functions are active.