Reactive power import (ANSI 40U)

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS
Protection IEC symbol (IEC60617) ANSI (IEEE C37.2) Operate time
Reactive power import (loss of excitation/under-excitation) Q<, Q<< 40U < 100 ms
The alarm response is based on the reactive power (Q) to the source, as measured and calculated by the controller. Reactive power import is when the generator is feeding a capacitive load. image/svg+xmlSet point Value time Delay

Common protect > Reactive power protect. > Loss of excitation > -Q>

Parameter Text Range Default
1521 Set point 0 to 150 % 50 %
1522 Timer 0.1 to 100 s 10 s
1525 Enable

OFF

ON

OFF
1526 Fail class Fail classes Warning