Over-voltage (ANSI 59)

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS
Protection IEC symbol (IEC60617) ANSI (IEEE C37.2) Operate time
Over-voltage U>, U>> 59 < 50 ms
The alarm response is based on the highest phase-to-phase voltage, or the highest phase-to-neutral voltage, from the source, as measured by the controller. image/svg+xmlSet point Value time Delay

Source 2 > Voltage protections > Over-voltage > S2 U> [1 to 3]

Parameter Text Range S2 U> 1 S2 U> 2 S2 U> 3
1271, 1281 or 1291 Set point 100 to 120 % 103 % 105 % 105 %
1272, 1282 or 1292 Timer 0.04 to 99.99 s 10 s 5 s 5 s
1275, 1285 or 1295 Enable

OFF

ON

OFF OFF OFF
1276, 1286 or 1296 Fail class Fail classes Warning Warning Warning

Source 2 > Voltage protections > Voltage detect. type

Parameter Text Range Default
1202 Type

Phase-Phase

Phase-Neutral

Phase-Phase