Voltage and frequency failures

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS

Voltage failures

Source 1 > U mains failure

Parameter Text Range Default
7061 S1 U failure 0.5 to 990 s 5 s
7062 S1 OK Delay U 2 to 9900 s 60 s
7063 S1 Low voltage 30 to 100 % 90 %
7064 S1 High voltage 100 to 120 % 110 %
7066 S1 Unbalanced Volt 2 to 100 % 100 %
7091 S1 Low Volt. Hyst. 0 to 70 % 0 %
7092 S1 High Volt Hyst. 0 to 20 % 0 %

Source 2 > U mains failure

Parameter Text Range Default
7101 S2 U failure 0.5 to 990 s 5 s
7102 S2 OK Delay U 2 to 9900 s 60 s
7103 S2 Low voltage 30 to 100 % 90 %
7104 S2 High voltage 100 to 120 % 110 %
7106 S2 Unbalanced Volt 2 to 100 % 100 %
7121 S2 Low Volt Hyst. 0 to 70 % 0 %
7122 S2 High Volt Hyst. 0 to 20 % 0 %

Frequency failures

Source 1 > f mains failure

Parameter Text Range Default
7071 S1 failure 0.5 to 990 s 5 s
7072 S1 OK Delay f 2 to 9900 s 60 s
7073 S1 Low Frequency 80 to 100 % 95 %
7074 S1 High Frequency 100 to 120 % 95 %
7093 S1 Low Freq. Hyst. 0 to 20 % 0 %
7094 S1 High Freq. Hyst. 0 to 20 % 0 %

Source 2 > f mains failure

Parameter Text Range Default
7111 S2 failure 0.5 to 990 s 5 s
7112 S2 OK Delay f 2 to 9900 s 60 s
7113 S2 Low Frequency 80 to 100 % 95 %
7114 S2 High Frequency 100 to 120 % 95 %
7123 S2 Low Freq. Hyst. 0 to 20 % 0 %
7124 S2 High Freq. Hyst. 0 to 20 % 0 %

Hysteresis

Hysteresis can be set for alarms for high and low nominal voltages and frequencies.

S1 high voltage example

A high voltage alarm has a set point of 110 % of nominal voltage for S1 and a S1 high voltage hysteresis of 7 %. This means the alarm cannot be reset until the S1 value falls below 103 % of the nominal voltage.

S2 low voltage example

A low voltage alarm with a set point of 70 % of the nominal voltage and a S1 low voltage hysteresis of 5.0 %. The alarm is only reset when the value is above 75.0 % of the nominal voltage.