The three-phase system is the default setting for the controller. When this is used, all
three phases must be connected to the controller.
The following configuration is required for three-phase measuring.
Basic settings > Nominal settings > Voltage > Source 1 nominal
U
| Parameter |
Text |
Range |
Adjust to value |
| 6004 |
Nom. U 1 |
100 to 25000 V |
UNOM |
Basic settings > Measurement setup > Voltage transformer > Source 1
VT
| Parameter |
Text |
Range |
Adjust to value |
| 6041 |
S1 primary U |
100 to 25000 V |
Primary VT |
| 6042 |
S1 secondary U |
100 to 690 V |
Secondary VT |
Basic settings > Nominal settings > Voltage > Source 2 nominal
U
| Parameter |
Text |
Range |
Adjust to value |
| 6053 |
S2 Nominal U 1 |
100 to 25000 V |
UNOM |
Basic settings > Measurement setup > Voltage transformer > Source 2
VT
| Parameter |
Text |
Range |
Adjust to value |
| 6051 |
S2 primary U 1 |
100 to 25000 V |
Primary VT |
| 6052 |
S2 second. U 1 |
100 to 690 V |
Secondary VT |
Note: The controller has two sets of busbar transformer settings, which can be
enabled individually in this measurement system.