Three-phase system

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS

The three-phase system is the default setting for the controller. When this is used, all three phases must be connected to the controller.

The following configuration is required for three-phase measuring.

Basic settings > Nominal settings > Voltage > Source 1 nominal U

Parameter Text Range Adjust to value
6004 Nom. U 1 100 to 25000 V UNOM

Basic settings > Measurement setup > Voltage transformer > Source 1 VT

Parameter Text Range Adjust to value
6041 S1 primary U 100 to 25000 V Primary VT
6042 S1 secondary U 100 to 690 V Secondary VT

Basic settings > Nominal settings > Voltage > Source 2 nominal U

Parameter Text Range Adjust to value
6053 S2 Nominal U 1 100 to 25000 V UNOM

Basic settings > Measurement setup > Voltage transformer > Source 2 VT

Parameter Text Range Adjust to value
6051 S2 primary U 1 100 to 25000 V Primary VT
6052 S2 second. U 1 100 to 690 V Secondary VT
Note: The controller has two sets of busbar transformer settings, which can be enabled individually in this measurement system.