Default nominal settings

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS

The default nominal settings are settings 1.

Basic settings > Nominal settings > Voltage

Parameter Text Range Default
6004 Voltage Nom. U 1 100 to 25000 V 400 V
6053 Voltage S2 Nominal U 1 100 to 25000 V 400 V

Basic settings > Nominal settings > Current

Parameter Text Range Default
6003 Current Nom. I 1 0 to 9000 A 867 A
6006 Current Nom. I E/N/M 1 0 to 9000 A 867 A
6001 Frequency Nom. f 1 48.0 to 62.0 Hz 50 Hz

Basic settings > Nominal settings > Power

6055 Power 4th CT nom. P 1 0 to 9000 kW 480 kW