Using an analogue output as a transducer

AGC 150 ATS Designers handbook

Name
agc-150-ats-designers-handbook-4189341346-uk
Product
AGC 150 ATS

You can configure transducers 52 and/or 55 to transmit values to an external system. The values include the controller's set points, and AC measurements.

You can select a scale for some of the values. For example, for the source 2 busbar B voltage (parameter 5913), select the minimum in 5915, and select the maximum in 5914.

Note: These values are also available using Modbus.

Transducer range

I/O settings > Outputs > Transducer > Output [52 or 55] limits

Parameter Name Range Details
5802 or 5812 AOUT [52 or 55] limits -10.5 to 5 V The transducer minimum limit.
5803 or 5813 AOUT [52 or 55] limits -5 to 10.5 V The transducer maximum limit.

Transducer configuration example: Power output

I/O settings > Outputs > Transducer > kW > P output actual

Parameter Name Range Details
5823 P1 output type Set point
  • Disabled
  • -10 to 10 V
Select the output.
Transducer A
  • Disabled
  • Transducer 52
  • Transducer 55
5824 P1 output max 0 to 20000 kW Busbar A active power maximum for the transducer
5825 P1 output min -9999 to 20000 kW Busbar A active power minimum for the transducer

Other transducer values

Parameter Name Details
5853, 5854, 5855 S Apparent power busbar A
5863, 5864, 5865 Q Reactive power busbar A
5873, 5874, 5875 PF Power factor
5883, 5884, 5885 f Busbar A frequency
5893, 5894, 5895 U Busbar A voltage
5903, 5904, 5905 I L1 current
5913, 5914, 5915 U S2 Busbar B voltage
5923, 5924, 5925 f S2 Busbar B frequency
5933, 5934, 5935 Input 20 The value received by analogue input 20.
5943, 5944, 5945 Input 21 The value received by analogue input 21.
5953, 5954, 5955 Input 22 The value received by analogue input 22.