The controller has 12 x DC relay outputs as standard. The outputs are divided in two groups with different electrical characteristics.
The outputs of relays 5 to 14 are configurable.
The outputs of relays 15 to 18 are not configurable.
Relay outputs, group 1
Electrical characteristics
- Voltage: 0 to 36 V DC
- Current: 15 A DC inrush, 3 A DC continuous
| Relay | ATS default setting |
|---|---|
| Relay 05 | Not used |
| Relay 06 | Not used |
Relay outputs, group 2
Electrical characteristics
- Voltage: 4.5 to 36 V DC
- Current: 2 A DC inrush, 0.5 A DC continuous
| Relay | ATS default setting |
|---|---|
| Relay 09 | Not used |
| Relay 10 | Not used |
| Relay 11 | Status OK |
| Relay 12 | Horn |
| Relay 13 | Not configurable |
| Relay 14 | Not configurable |
| Relay 15 | Not configurable |
| Relay 16 | Not configurable |
| Relay 17 | Not configurable |
| Relay 18 | Not configurable |