The digital inputs can be configured from the controller or with the utility software (some parameters can only be accessed with the utility software).
I/O settings > Inputs > Digital input > Digital input [39 to
50]
| Parameter | Text | Range | Default |
|---|---|---|---|
| 3001, 3011, 3021, 3031, 3041, 3051, 3061, 3071, 3081, 3091, 3101 or 3111 | Delay | 0.0 to 3200 s | 10.0 s |
| 3002, 3012, 3022, 3032, 3042, 3052, 3062, 3072, 3082, 3092, 3102 or 3112 | Output A | Relays and M-Logic | Not used |
| 3003, 3013, 3023, 3033, 3043, 3053, 3063, 3073, 3083, 3093, 3103 or 3113 | Output B | Relays and M-Logic | Not used |
| 3004, 3014, 3024, 3034, 3044, 3054, 3064, 3074, 3084, 3094, 3104 or 3114 | Alarm |
Disable Enable |
Disable |
| 3005, 3015, 3025, 3035, 3045, 3055, 3065, 3075, 3085, 3095, 3105 or 3115 | Fail class | Fail classes | Warning |
| 3006, 3016, 3026, 3036, 3046, 3056, 3066, 3076, 3086, 3096, 3106 or 3116 | Type |
High Low |
High |
Configure a digital input with the utility software
In the utility software, in I/O & Hardware setup, select the digital input to configure.
| No. | Text | Description |
|---|---|---|
| 1 | Preconfigured function | Select a function for the digital input. |
| 2 | Alarm | Activates or deactivates the alarm function. |
| 3 | Display text | Select the display text. This is also shown on the display. |
| 4 | High alarm | The alarm is activated when the signal is high. |
| 5 | Timer | The timer setting is the time from the alarm level is reached until the alarm occurs. |
| 6 | Fail class | Select the required fail class from the list. When the alarm occurs, the controller reacts according to the selected fail class. |
| 7 | Output A | Select the terminal (or the limit option) to be activated by an alarm. Limit makes the alarm useable as an input event in M-Logic. |
| 8 | Output B | Select the terminal (or the limit option) to be activated by an alarm. Limit makes the alarm useable as an input event in M-Logic. |
| 9 | Auto acknowledge | If this option is set, the alarm is automatically acknowledged if the signal related to the alarm disappears. |
| 10 | Inhibits | Select the exceptions to when an alarm must be activated. To select when the alarms are to be active, each alarm has a configurable inhibit setting. |
| 11 | Password level | Select the password level that is needed to modify this parameter (cannot be edited by a user with lower privileges). |
Click on the Write to device
button to write the settings to the controller.