Protections overview

AGC 150 Generator Mains BTB Data sheet

Name
agc-150-generator-mains-btb-data-sheet-4921240618-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator
Protections Alarms ANSI Operate time Genset* Mains BTB
Reverse power 3 32R <200 ms
Fast over-current 2 50P <40 ms
Over-current 4 50TD <200 ms
Voltage dependent over-current 1 50V  
Over-voltage 2 59 <200 ms
Under-voltage 3 27P <200 ms
Over-frequency 3 81O <300 ms
Under-frequency 3 81U <300 ms
Unbalanced voltage 1 47 <200 ms
Unbalanced current 1 46 <200 ms
Under-excitation or reactive power import 1 32RV <200 ms    
Over-excitation or reactive power export 1 32FV <200 ms    
Overload** 5 32F <200 ms
Inverse time earth over-current 1 50G <100 ms
Inverse time neutral over-current 1 50N <100 ms
Busbar/mains over-voltage 3 59P <50 ms
Busbar/mains under-voltage 4 27P <50 ms
Busbar/mains over-frequency 3 81O <50 ms
Busbar/mains under-frequency 3 81U <50 ms
Emergency stop 1   <200 ms    
Low auxiliary supply 1 27DC  
High auxiliary supply 1 59DC  
Generator breaker external trip 1        
Tie breaker external trip 1      
Mains breaker external trip 1        
Synchronisation failure alarms 1/breaker    
Breaker open failure 1/breaker 52BF  
Breaker close failure 1/breaker 52BF  
Breaker position failure 1/breaker 52BF  
Close before excitation failure 1        
Phase sequence error 1 47  
De-load error 1        
Hz/V failure 1        
Not in Auto 1    
Vector shift 1 78 <40 ms  
ROCOF df/dt 1 81R <130 ms
Under-voltage and reactive power, U and Q 2   <250 ms  
Positive sequence (mains) voltage low 1 27 <60 ms  
Directional over-current 2 67 <100 ms  
Negative sequence voltage high 1 47 <400 ms  
Negative sequence current high 1 46I2 <400 ms  
Zero sequence voltage high 1 59U0 <400 ms  
Zero sequence current high 1 50I0 <400 ms  
Power-dependent reactive power 1 40 -    
IEC/IEEE inverse time over-current 1 51 -  
Neutral inverse time over-current (4th CT) 1 51N -
Earth fault inverse time over-current (4th CT) 1 51G -
Neutral over-current (4th CT) 2 - -
Earth fault over-current (4th CT) 2 - -
Note: * See Generator controller functions for engine protections.
Note: **You can configure these protections for overload or reverse power.