Display, buttons and LEDs

Operator's manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator
No. Name Function
1 Power

Green: The controller power is ON.

OFF: The controller power is OFF.

2 Display screen

Resolution: 240 x 128 px.

Viewing area: 88.50 x 51.40 mm.

Six lines, each with 25 characters.

3 Navigation Move the selector up, down, left and right on the screen.
4 OK

Go to the Menu system.

Confirm the selection on the screen.

5 Back Go to the previous page.
6 AUTO mode

For BTB controllers, the controller automatically joins and splits the busbar. No operator actions are needed. The controllers use the power management configuration to automatically select the power management action.

7 Silence horn Stops an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the Jump menu, Lamp test.
9 SEMI-AUTO mode

The operator or an external signal can join or split the busbar. The BTB controller cannot automatically join or split the busbar.

The controller automatically synchronises before closing a breaker, and automatically deloads before opening a breaker.

11 Close breaker Push to close the breaker.
12 Open breaker Push to open the breaker.
13 Breaker symbols

Green: Breaker is closed.

Green flashing: Synchronising or deloading.

Red: Breaker failure.