Running modes

AGC 150 Generator Mains BTB Operators manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator

The BTB controller has three running modes. To configure the running mode push the Shortcut image/svg+xml button and select Running Modes.

Mode Description
AUTO The controller automatically joins and splits the busbar. The operator cannot start a sequence manually. The controllers use the power management configuration to automatically select the power management action.
MANUAL The controller cannot automatically join and split the busbar. The operator or an external signal can start these sequences. The controller automatically synchronises before closing a breaker, and automatically de-loads before opening a breaker.
BLOCK The controller cannot start sequences. Select the block mode when you do maintenance work.