Running modes

Operator's manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator

The AGC 150 BTB controller has three running modes. To configure the running mode push the Shortcut image/svg+xml button and select Running Modes.

Mode Description
AUTO The controller automatically joins and splits the busbar. The operator cannot start a sequence manually. The controllers use the power management configuration to automatically select the power management action.
SEMI-AUTO The controller cannot automatically join and split the busbar. The operator or an external signal can start these sequences. The controller automatically synchronises before closing a breaker, and automatically de-loads before opening a breaker.
BLOCK The controller cannot start sequences. Select the block mode when you do maintenance work.