Display, buttons and LEDs

Operator's manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator
No. Name Function
1 Power

Green: The controller power is ON.

OFF: The controller power is OFF.

2 Display screen

Resolution: 240 x 128 px.

Viewing area: 88.50 x 51.40 mm.

Six lines, each with 25 characters.

3 Navigation Move the selector up, down, left and right on the screen.
4 OK

Go to the Menu system.

Confirm the selection on the screen.

5 Back Go to the previous page.
6 AUTO mode

For generator controllers, the controller automatically starts and stops (and connects and disconnects) gensets. No operator actions are needed. The controllers use the power management configuration to automatically select the power management action.

7 Silence horn Stops an alarm horn (if configured) and enters the Alarm menu.
8 Shortcut menu Access the Jump menu, Mode selection, Test, Lamp test.
9 SEMI-AUTO mode

The operator or an external signal can start, stop, connect or disconnect the genset. The generator controller cannot automatically start, stop, connect or disconnect the genset.

The controller automatically synchronises before closing a breaker, and automatically deloads before opening a breaker.

10 Mains symbol

Green: Mains voltage and frequency are OK. The controller can synchronise and close the breaker.

Red: Mains failure.

11 Close breaker Push to close the breaker.
12 Open breaker Push to open the breaker.
13 Breaker symbols

Green: Breaker is closed.

Green flashing: Synchronising or deloading.

Red: Breaker failure.

14 Generator

Green: Generator voltage and frequency are OK. The controller can synchronise and close the breaker.

Green flashing: The generator voltage and frequency are OK, but the V&Hz OK timer is still running. The controller cannot close the breaker.

Red: The generator voltage is too low to measure.

15 Engine

Green: There is running feedback.

Green flashing: The engine is getting ready.

Red: The engine is not running, or there is no running feedback.

16 Stop Stops the genset if SEMI-AUTO or Manual is selected.
17 Start Starts the genset if SEMI-AUTO or Manual is selected.
18 Load symbol

OFF: Power management application.

Green: The supply voltage and frequency are OK.

Red: Supply voltage/frequency failure.