Mimic function

Operator's manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator

Parameters > Basic settings > Controller settings > Display > LED mimic

Parameter no. Item Range
6082 LED mimic

Standard with genset

Standard

Guided with genset

Guided

Standard

The control buttons and LEDs are shown.

If you stop the genset, the motor/generator symbols are not shown.

Standard with genset

The control buttons and LEDs are shown.

If you the stop the genset, the motor/generator symbols are shown in red.

Guided

Active control buttons and LEDs are shown inactive are not shown.

Example: The controller is in SEMI-AUTO mode, and the genset is not operating. Only the start button is shown, as this is the only possible action.

image/svg+xml

Guided with genset

Active control buttons, LEDs and the motor/generator symbols are shown, inactive are not shown.

Example: The controller is in SEMI-AUTO mode. The genset is not operating. The only possible action is to start the genset, and so only the start button and the red motor/generator symbols are shown.

All Mimic settings
The breaker symbol is shown in red:
  • Breaker position failure
  • Breaker close failure
The breaker symbol flashes green:
  • The controller is synchronising
  • The controller is de-loading