| No. | Name | Function |
|---|---|---|
| 1 | Power |
Green: The controller power is ON. OFF: The controller power is OFF. |
| 2 | Display screen |
Resolution: 240 x 128 px. Viewing area: 88.50 x 51.40 mm. Six lines, each with 25 characters. |
| 3 | Navigation | Move the selector up, down, left and right on the screen. |
| 4 | OK |
Go to the Menu system. Confirm the selection on the screen. |
| 5 | Back | Go to the previous page. |
| 6 | AUTO mode |
For mains controllers, the controller automatically connects and disconnects the mains. No operator actions are needed. The controllers use the power management configuration to automatically select the power management action. |
| 7 | Silence horn | Stops an alarm horn (if configured) and enters the Alarm menu. |
| 8 | Shortcut menu | Access the Jump menu, Mode selection, Test, Lamp test. |
| 9 | SEMI-AUTO mode |
The operator or an external signal can connect or disconnect the mains. The mains controller cannot automatically connect or disconnect the mains. The controller automatically synchronises before closing a breaker, and automatically deloads before opening a breaker. |
| 10 | Mains symbol |
Green: Mains voltage and frequency are OK. The controller can synchronise and close the breaker. Red: Mains failure. |
| 11 | Close breaker | Push to close the breaker. |
| 12 | Open breaker | Push to open the breaker. |
| 13 | Breaker symbols |
Green: Breaker is closed. Green flashing: Synchronising or deloading. Red: Breaker failure. |
| 16 | Stop | Stops the plant. |
| 17 | Start | Starts the plant. |
| 18 | Load symbol |
OFF: Power management application. Green: The supply voltage and frequency are OK. Red: Supply voltage/frequency failure. |