Running modes

Operator's manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator

The AGC 150 Mains controller has three running modes, and a test mode. Push the Shortcut image/svg+xml button and select Running Modes to configure the mode. Configure the test mode in Settings > Power set points > Test. To run the test push the Shortcut image/svg+xml button and select Start Test.

Mode Description
AUTO The controller automatically connects and disconnects the mains. The operator cannot start a sequence manually. The controllers use the power management configuration to automatically select the power management action.
SEMI-AUTO The controller cannot automatically connect and disconnect the mains. The operator or an external signal can start these sequences. The controller automatically synchronises before closing a breaker, and automatically de-loads before opening a breaker.
Test The test sequence starts when you select the test mode.
BLOCK The controller cannot start sequences. Select the block mode when you do maintenance work.