Running modes

AGC 150 Generator Mains BTB Operators manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator

The Mains controller has three running modes, and a test mode. Push the Shortcut image/svg+xml button and select Running Modes to configure the mode. Configure the test mode in Settings > Power set points > Test. To run the test push the Shortcut image/svg+xml button and select Start Test.

Mode Description
AUTO The controller automatically connects and disconnects the mains. The operator cannot start a sequence manually. The controllers use the power management configuration to automatically select the power management action.
MANUAL The controller cannot automatically connect and disconnect the mains. The operator or an external signal can start these sequences. The controller automatically synchronises before closing a breaker, and automatically de-loads before opening a breaker.
Test The test sequence starts when you select the test mode.
BLOCK The controller cannot start sequences. Select the block mode when you do maintenance work.