The AGC 150 Mains controller has three running modes, and a test mode. Push the
Shortcut
button and select Running Modes to configure the mode. Configure the test mode
in Settings > Power set points > Test. To run the test push the
Shortcut
button and select Start Test.
| Mode | Description |
|---|---|
| AUTO | The controller automatically connects and disconnects the mains. The operator cannot start a sequence manually. The controllers use the power management configuration to automatically select the power management action. |
| SEMI-AUTO | The controller cannot automatically connect and disconnect the mains. The operator or an external signal can start these sequences. The controller automatically synchronises before closing a breaker, and automatically de-loads before opening a breaker. |
| Test | The test sequence starts when you select the test mode. |
| BLOCK | The controller cannot start sequences. Select the block mode when you do maintenance work. |