If the function Alarm Jump is on, the controller automatically shows the alarm list on the display screen when an alarm occurs.
Service View > Display > Alarm Jump
| Parameter | Text | Range | Default |
|---|---|---|---|
| 9157 | Alarm Jump |
OFF ON |
ON |
Access the alarm list from the controller
- From the view menu, push the button.
- Use the and buttons to go to the Alarm list.
- Push the button to view the Alarm list.
- Push the button to go back.
The alarm list contains both acknowledged and unacknowledged alarms that are active. An alarm is active, if you have not cleared the alarm condition, which started the alarm. Once an alarm is acknowledged and you have cleared the alarm condition, the alarm is removed from the alarm list. If there are no alarms, then the alarm list shows No alarms.
The display screen can show only one alarm at a time. The number of alarms is shown on the right at the bottom of the screen.
Example of an unacknowledged alarm
To see the other alarms, use the and buttons to go through the list. To acknowledge an alarm, select the alarm and push the button.
Access the alarm list with the utility Software
Select Alarms from the left toolbar.| CAUTION | |
|---|---|