The AGC 150 Generator controller contains all the functions needed to protect and control a genset, and the genset breaker. If you do not use power management, the controller can also protect and control the mains breaker.
The AGC 150 Mains controller protects and controls a mains breaker, and a tie breaker.
The AGC 150 BTB controller protects and controls a bus tie breaker. The power management system manages the busbar sections.
Power management system
AGC 150 controllers can work together in a power management system (PMS). This includes synchronisation, island operation, and running parallel to mains. The PMS can automatically start and stop gensets, and open and close breakers. You can also use AGC 150 in power management systems with other DEIF controllers.
Buttons and LEDs
Use the buttons to operate the system. You can change running modes, stop alarms, see the shortcut menu, and navigate the controller. You can only use the start and stop buttons and the buttons to open and close the breakers in SEMI-AUTO mode and manual mode. Use the mimic function to select how the control buttons and LEDs are shown on the controller's display.
Display screen
- See the operating status
- See the alarms and logs list
- Monitor the exhaust after-treatment (Tier 4/Stage V)
- Configure the controller settings and parameters