Status texts

Operator's manual

Name
agc-150-generator-mains-btb-operators-manual-4189341312-uk
Product
AGC 150 Mains
AGC 150 BTB
AGC 150 Generator
Status text Condition
ACCESS LOCK The configurable input is activated, and the operator tries to activate one of the blocked keys.
ADAPT IN PROGRESS Power management: The controller is receiving the application it has connected to.
AMF ACTIVE The controller is in auto mode during a mains failure.
AMF AUTO The mains controller is in auto mode and ready to respond.
AMF MAN The controller is in manual mode and waiting for operator input.
AMF SEMI The controller is in semi-automatic mode and waiting for operator input.
AUTO OPERATION BTB power management: BTB controller is in AUTO mode, but is not ready for breaker operation (because of an active BTB trip alarm).
Aux. test ##.#V ####s The battery test is activated.
BLACKOUT ENABLE Generator power management: CAN failure in a power management application.
BLOCK Block mode is activated.
BLOCKED FOR CLOSING BTB power management: Last open BTB in a ring bus.
BROADCAST ABORTED Power management: Broadcast terminated.
BROADCASTING APPL. # Power management: Broadcast one of the four applications from one controller to the other controllers in the power management system, through the CAN line.
BROADCAST COMPLETED Power management: Correct broadcast of an application.
BTB TRIP EXTERNALLY BTB power management: External equipment has tripped the breaker, and this is logged in the event log.
BTB XX DIVIDING SEC. Generator power management: BTB XX is dividing two sections in an island application.
COMPENSATION FREQ. Compensation is active. The frequency is not at the nominal setting.
COOLING DOWN ###s Cooling-down period is activated.
DELOAD The controller is decreasing the load of the genset in order to open the breaker.
DELOADING BTB XX Generator power management: Genset controllers are load sharing asymmetrically to de-load BTB XX.
DERATED TO #####kW Displays the ramp-down set point.
DG BLOCKED FOR START The generator has stopped and has active alarm(s).
DIVIDING SECTION BTB power management: A BTB unit is dividing two sections in an island application.
EXT. START ORDER A planned AMF sequence is activated (without a mains failure).
EXT. STOP TIME ###s The extended stop timer is running.
FIXED POWER ACTIVE The controller is in auto mode and supplying fixed power.
FIXED POWER AUTO The mains controller is in auto mode and ready to respond.
FIXED POWER MAN The controller is in manual mode and waiting for operator input.
FIXED POWER SEMI The controller is in semi-automatic mode and waiting for operator input.
FULL TEST Test mode is activated.
FULL TEST ###.#min Test mode is activated and test timer counting down.
GB ON BLOCKED The generator is running, the GB is open and there is an active Trip GB alarm.
GB TRIP EXTERNALLY Some external equipment has tripped the breaker. An external trip is logged in the event log.
GENSET STOPPING Cooling down has finished.
Hz/V OK IN ###s The voltage and frequency on the genset is OK. When the timer runs out the generator breaker can be closed.
IDLE RUN The Idle run function is active. The genset does not stop until a timer has expired.
IDLE RUN ###.#min The Idle run function is active. The genset does not stop until the timer has expired.
ISLAND ACTIVE The controller is in auto mode and supplying power while not connected to a mains supply.
ISLAND AUTO The mains controller is in auto mode and ready to respond.
ISLAND MAN The controller is in manual mode and waiting for operator input.
ISLAND SEMI The controller is in semi-automatic mode and waiting for operator input.
Loadshare conf error Analogue load sharing is selected, but there is no IOM.
LOAD TAKE OVER AUTO The mains controller is in auto mode and ready to respond.
LOAD TAKE OVER MAN The controller is in manual mode and waiting for operator input.
LOAD TAKE OVER SEMI The controller is in semi-automatic mode and waiting for operator input.
LOAD TEST Test mode is activated.
LOAD TEST ###.#min Test mode is activated and test timer counting down.
LTO ACTIVE The controller is in auto mode and taking over the load.
MAINS FAILURE Mains failure and mains failure timer expired.
MAINS FAILURE IN ###s The frequency or voltage measurement is outside the limits. The timer shown is the mains failure delay.
MAINS f OK DEL ####s Mains frequency is OK after a mains failure. The timer shown is the mains OK delay.
MAINS P EXPORT AUTO The mains controller is in auto mode and ready to respond.
MAINS P EXPORT MAN The controller is in manual mode and waiting for operator input.
MAINS P EXPORT SEMI The controller is in semi-automatic mode and waiting for operator input.
MAINS U OK DEL ####s The mains voltage is OK after a mains failure. The timer shown is the mains OK delay.
MB TRIP EXTERNALLY Power management: Some external equipment (not the controller) has tripped the breaker. An external trip is logged in the event log.
MOUNT CAN CONNECTOR Power management: Connect the power management CAN line.
MPE ACTIVE The controller is in auto mode and exporting power to the mains.
PEAK SHAVING ACTIVE The controller is in auto mode and doing peak shaving.
PEAK SHAVING AUTO The mains controller is in auto mode and ready to respond.
PEAK SHAVING MAN The controller is in manual mode and waiting for operator input.
PEAK SHAVING SEMI The controller is in semi-automatic mode and waiting for operator input.
QUICK SETUP ERROR Power management: Failure of the quick setup of the application.
RAMP TO #####kW The power ramp is ramping in steps. The next step that is reached after the timer has expired is displayed.
READY AMF AUTO The genset controller is in auto mode and the genset is stopped.
READY AUTO OPERATION BTB power management: BTB unit in AUTO mode and ready for breaker operation (no active BTB trip alarm).
READY FIXED P AUTO The genset controller is in auto mode and the genset is stopped.
READY ISLAND AUTO The genset controller is in auto mode and the genset is stopped.
READY LTO AUTO The genset controller is in auto mode and the genset is stopped.
READY MPE AUTO The genset controller is in auto mode and the genset is stopped.
READY PEAK SHAV AUTO The genset controller is in auto mode and the genset is stopped.
RECEIVING APPL. # Power management: The controller is receiving an application.
RECEIVE COMPLETED Power management: Application received correctly.
RECEIVE ERROR Power management: Application is not received correctly.
REMOVE CAN CONNECTOR Power management: Remove the power management CAN lines.
SELECT GENSET MODE Power management is deactivated and no other genset mode is selected.
SEMI OPERATION BTB power management: BTB unit in SEMI-AUTO mode.
SETUP COMPLETED Power management: Correct update of the application in all controllers.
SETUP IN PROGRESS Power management: The new controller is being added to the existing application.
SHUTDOWN OVERRIDE The configurable input is active.
SIMPLE TEST Test mode is activated.
SIMPLE TEST ###.#min Test mode is activated and test timer counting down.
START DG(s) IN ###s The start genset set point has been exceeded. The genset starts when the timer expires.
START PREPARE The start prepare relay is activated.
START RELAY OFF The start relay is deactivated during the start sequence.
START RELAY ON The start relay is activated.
STOP DG(s) IN ###s The stop genset set point has been exceeded. The genset stops when the timer expires.
SYNCHRONISING BTB XX Generator power management: BTB XX is synchronising.
SYNCHRONISING MB XX Generator power management: MB XX is synchronising.
SYNCHRONISING TB XX Generator power management: TB XX is synchronising.
TB TRIP EXTERNALLY Mains power management: External equipment has tripped the breaker, and this is logged in the event log.
TOO SLOW 00<------------- Generator running too slow during synchronisation.
-----------> 00 TOO FAST Generator running too fast during synchronisation.
UNEXPECTED GB ON BB Another generator breaker is closed on to the busbar (due to a GB position failure) while no voltage is present on the busbar. This shows that other breakers cannot close to the busbar because of position failure on one or more GBs.
UNIT STANDBY Generator and Mains power management: If there are redundant mains controllers, this is shown on the redundant controller.
WARM UP RAMP Warm up ramp is active. The available power is limited until the pre-defined temperature is reached, or when the input that activated warm up ramp is deactivated.
---xx-------- >00< ------------ Generator is synchronising. The "xx" marks the actual generator phase angle position in the synchronisation. When the "xx" is aligned over the 00 centre, the generator is synchronised.