The ASC uses these data formats:
- AB: 16-bit values.
- ABCD: 32-bit values. These are represented as with HI16 on lowest address and LO16 on highest address.
|
32-bit value format example The PV active power reference is INT32s data, with data format ABCD, in Modbus address 46000 under Holding register (03;06;16). Modbus address 46000 contains HI16 for PV active power reference. Modbus address 46001 contains LO16 for PV active power reference. |