RS-485

User manual

Name
asc-150-modbus-server-user-manual-4189341366-uk
Product
ASC 150 Storage

Communication > RS485 > RS485 [1 or 2] > Settings

Parameter Name Range Default Details
7511 or 7521 Ext. comm. ID [1 or 2] 1 to 247 3 Modbus communication ID for the ASC Modbus server. The external Modbus client uses this ID to communicate with the ASC.
7512 or 7522 Ext. comm.speed[1 or 2]
  • 9600 Baud
  • 19200 Baud
  • 38400 Baud
  • 115200 Baud
9600 Baud Communication speed for RS-485 [1 or 2]

Communication > RS485 > RS485 [1 or 2] > Communication error

Parameter Name Range Default Details
7513 or 7523 Timer 1 to 100 s 10 s Communication error for RS-485 [1 or 2]
7516 or 7526 Enable
  • OFF
  • ON
OFF
7517 or 7527 Fail class Fail classes Warning