Communication > RS485 > RS485 [1 or 2] > Settings
| Parameter | Name | Range | Default | Details |
|---|---|---|---|---|
| 7511 or 7521 | Ext. comm. ID [1 or 2] | 1 to 247 | 3 | Modbus communication ID for the ASC Modbus server. The external Modbus client uses this ID to communicate with the ASC. |
| 7512 or 7522 | Ext. comm.speed[1 or 2] |
|
9600 Baud | Communication speed for RS-485 [1 or 2] |
Communication > RS485 > RS485 [1 or 2] > Communication
error
| Parameter | Name | Range | Default | Details |
|---|---|---|---|---|
| 7513 or 7523 | Timer | 1 to 100 s | 10 s | Communication error for RS-485 [1 or 2] |
| 7516 or 7526 | Enable |
|
OFF | |
| 7517 or 7527 | Fail class | Fail classes | Warning |